The Diseases Of Electrical Machinery
Forfatter: Ernst Schulz
År: 1904
Forlag: E. & F. N. SPON, Ltd.
Sted: London
Sider: 84
UDK: 621.311
Edited with a preface, by Silvanus P. Thompson
Søgning i bogen
Den bedste måde at søge i bogen er ved at downloade PDF'en og søge i den.
Derved får du fremhævet ordene visuelt direkte på billedet af siden.
Digitaliseret bog
Bogens tekst er maskinlæst, så der kan være en del fejl og mangler.
4+
THE DIS EAS ES OF
will happen in this case, one will find that the motor
may start without load, but not with load. The further
the starting lever is turned the more the shunt current
is diminished, until finally no current at all flows
through the magnet. The motor will then either run
L. N. A.
Fig. 26.
<www
away, sparking furiously, or
else stop dead and burn out.
A further false method
of connection is shown in
Fig. 26. Here the terminals
A and L have been inter-
changed. The result is that
the shunt current is much
weakened at starting, where-
fore in most cases the motor will not start. If it
does run, however, it will then run better from con-
tact to contact, until finally the end contact is reached,
when it is then correctly connected. In this case the
fault occurs which is represented in Fig. 21.
Various other Faults.—We have now said
enough on this subject, and turn to the last division
of our catalogue of the faults of continuous-current
machines. We will here consider different causes of
trouble which do not fali under any of the above head-
ings. A fault which often occurs is the loss of the
remanent magnetism of a machine. This may be
caused in two ways; first, owing to the machine not
having been used for a long time, and secondly,
through false magnetisation of the poles.