 74 THE DISEA SES OF is 142 volts, the two single-phase transformers must be built for 100 volts. With star-connected three- phase transformers, with a voltage of 173 volts be- tween lines, the separate transformers must be built for 100 volts. If the line voltage is 1000 volts, each of the star-connected transformers must be of 577 volts. If the transformers are connected in mesh, the line voltage is equal to the voltage of a single trans- Fig. 40. former. In Figs. 30, 36 and 37, the various voltages have been inserted. Two-phase and three-phase transformers can, how- ever, also be built by combining mechanically in one system a corresponding number of single-phase trans- formers. Numerous firms have built three-phase transformers as in Fig. 38. These are three-leg core transformers. The difference between them and the single-phase shell-type (Fig. 33) is, that the section of the three legs is the same, and that all the three are